NEC 422

NEC Article 422 — Appliances: Dedicated Circuits, Disconnects, and the Dishwasher GFCI Rule

NEC 422 governs appliances. Dishwasher and disposal need dedicated circuits, dishwasher needs GFCI per the 2020 NEC, and every appliance needs a way to disconnect for service.

By Michael Malfettone, Licensed NJ Master Electrician · Malfettone Electric LLC · Family-owned since 1977

NEC 422 covers appliances — the rules for hardwired and cord-connected loads in dwellings. The most-cited sub-rules:

Dishwasher GFCI required (422.5(A) / 210.8 expansion): since the 2020 NEC, dishwashers (whether hardwired or cord-and-plug connected) must be GFCI-protected. The protection can be at the receptacle, at a GFCI breaker, or at a GFCI device upstream. NJ adopted this with the 2023 NEC update.

Disposal disconnect (422.31(B)): every motor-operated appliance over ⅛ HP needs a disconnect within sight of the motor or a lockable breaker. Most kitchen disposals (½ HP, 1 HP) trigger this. The under-sink toggle switch satisfies it for cord-and-plug units.

Range circuit (422.10): electric ranges need a dedicated branch circuit. NEC 220.55 sets the demand factor for the load calculation (typically 8 kW for a single household range up to 12 kW nameplate).

Dryer circuit (422.10 + 220.54): electric clothes dryers need a dedicated 30 A branch circuit minimum. Load calc: minimum 5,000 VA per dwelling unit per 220.54.

Water heater (422.13): electric water heaters are continuous loads. The branch circuit must be sized at 125% of the nameplate. Most 4,500 W water heaters draw 18.75 A continuous, requiring a 30 A breaker and #10 CU minimum (often #8 CU on long runs for voltage drop).

Microwave / cooktop / wall oven — each gets its own dedicated 20 A or 30 A circuit. Counter-top microwaves on the appliance circuit are technically allowed but discouraged for nuisance-trip reasons.

Built-in appliance height for over-current protection (422.31): the disconnect / overcurrent device for any built-in appliance must be readily accessible. A breaker panel in the same room (or visible from it) usually satisfies this.

The NJ-specific microwave footprint: older Hoboken brownstones often have undersized service, and adding a high-wattage microwave puts the kitchen circuit over 80% loading. Run the load calc before adding ANY new dedicated kitchen circuit on a service that's already under stress.

For the load-calc impact of new appliances, use the free Malfettone Load Calculator at /tools/load-calculator. It has presets for water heater, dishwasher, disposal, range, dryer, microwave, and the demand factors per Table 220.55.

Where this rule shows up in our work
Appliance circuits and repairs in Northern NJ
Dedicated appliance circuits, disconnects and repairs by a licensed NJ electrician.
Appliance circuits and repairs →

This guide is an educational summary written by a licensed NJ master electrician. It is not a substitute for the National Electrical Code or for the judgment of your local AHJ. For real permit work, verify every code interpretation with your authority having jurisdiction and a licensed electrician of record.